How can we help you today?

Can I use a mix of single phase and three phase in Tesys Island Avatars?

Issue:
Need to know if it is possible to mix single-phase and 3-phase loads in Tesys Island.

Product Line:
Motor Management system Tesys Island

Environment:
IEC Contactors and Starters

Resolution:
Yes, you can use a mixture of single phase and three phase Avatars in your system. If doing this, you must configure the "island" (VIM) as three-phase, and wire it A-B-C. Then for any single-phase avatars, they must be wired with phase A in the line 1 connection and phase C in the line 3 connection. The single-phase voltage must be Line-Line. At the moment TeSys island does not support energy monitoring for single-phase voltages L-N if the entire system is three-phase.

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings