Can I use a mix of single phase and three phase in Tesys Island Avatars?

Issue:
Need to know if it is possible to mix single-phase and 3-phase loads in Tesys Island.

Product Line:
Motor Management system Tesys Island

Environment:
IEC Contactors and Starters

Resolution:
Yes, you can use a mixture of single phase and three phase Avatars in your system. If doing this, you must configure the "island" (VIM) as three-phase, and wire it A-B-C. Then for any single-phase avatars, they must be wired with phase A in the line 1 connection and phase C in the line 3 connection. The single-phase voltage must be Line-Line. At the moment TeSys island does not support energy monitoring for single-phase voltages L-N if the entire system is three-phase.