Why does the HDPM6000 have duplicate Modbus registers listed

Issue:

Why does the HDPM6000 have duplicate Modbus registers listed?

Product Line:

HDPM6000

Environment:

HDPM6000 Modbus Register Map

Cause:

The Modbus Register list provides two Modbus registers with the same alarm register with two different Modbus register addresses.

For example: 10220-10227 - Warning and 10820-10831 - Warning.

What is the difference for these two sets of alarm registers?

Resolution

Some registers are legacy and only support up to 120 circuits.  (i.e. 10220-10227)

The new registers now support the new features of the HDPM6000 and a total of 192 Circuits. (i.e. 10820-10831)

HDPM6000 Protocol and Modbus Guide: PowerLogic™ HDPM6000 Protocol Guide | Schneider Electric