How can we help you today?

How to perform a full factory reset of Tesys island?

Issue:
How to return Tesys Island to factory settings?

Product Line:
Motor Management system Tesys Island

Environment:
IEC Contactors and Starters

Resolution:
The TeSys™ island system can be reset to factory settings, returning the bus coupler to its out-of-the-box conditions. This is useful, for example, to quickly get to Test mode when building or modifying an island.

TeSys island accepts a Factory Reset command from the digital tool (TeSys island DTM or OMT) with exclusive control when the system is in Pre-Operational mode, Test mode, or Minor Event state. Upon receiving a Factory Reset command, TeSys island

1. Deletes the following files:
• system context files (active, pending, and SDP if present)
• SEDP files (including active, pending, or update)
• Users file

2. Automatically restarts

NOTE: When the Users file is deleted, any added users are removed. In addition, the group management and the administrative password are reset to default values. A Factory Reset command does not delete log files.

To perform a factory reset using the TeSys island DTM, follow the steps below:
1. In the TeSys island DTM, select Device > Factory Reset.
2. Click OK to perform the factory reset. • The island starts the reset procedure. • The PWR LED on the bus coupler is yellow. • The LEDs on the rest of the modules flash green.

Using the TeSys island OMT
To perform a factory reset using the OMT, follow the steps below:
1. Click the Admin Options panel.
2. Expand the System Settings section.
3. Click the Restore Factory Defaults button.
4. Click OK to continue with the factory reset. • The island starts the reset procedure. • The PWR LED on the bus coupler is yellow. • The LEDs on the rest of the modules flash green.

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings