How can we help you today?

Missing the +10v supply on a ATV630/ATV930 drive

Issue:

Missing the +10v supply on a ATV630/ATV930 drive

Product Line:

ATV630/ATV930

Environment:

Missing +10v supply

Cause:

n/a

Resolution:

Would suggest to check the incoming power at L1, L2 and L3.

Then check the DC bus at PA/+ to PC/-.

If these are both ok, then measure between 24v and 0v for 24v.

Then measure between +10v to com and if all the supplies are ok, except the +10v, then appears the Main Control Board is inoperative.

Note: The Main Control Board would need to be replaced by Schneider-Electric Field Services

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings