How to install and remove option card on ATV630 and ATV930 Drives.

Issue:
How do I install an extended IO extension or Communication card on Altivar Process Drive?

Product Line:
ATV930, ATV630

Environment:
All

Cause:
NA

Resolution:
There are 2 Slots (A and B) underneath Control Terminal Blocks.
Slot A is on the right and Slot B is on the left as you are facing the VFD.
Slot A ids only used for Communication cards.
Slot B is only used for IOP Extension modules.
Slide the option card straight into the slot until hear a click.

In order to remove the card, press or push on the tab (PUSH is written on the tab) on the option card and slide it out.