Can SDSA1175 be connected on single pole breaker?

Issue:

Breaker to feed SPD SDSA1175

Product Line:

Surge Protection Device

Answer:

It has to be 2 single pole breakers

Make sure to have the SPD connected to breakers with opposing phases, one is on A phase and the other on B phase.

Have this installation approved by their electrical inspector first before doing that.

Schneider Electric USA