Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
EADM does not reflect PLC in NOCONF state when using EADM V3.1 or coming V3.2 to connect M340/PRA
Description:
  • When an M340 or BMXPRA PLC is in a "NOCONF" state and upon connecting via FTP or USB on EADM: --> the "Mode" section in Device List only shows "NOCONF" for a few seconds and then displays "STOP".
Expected/Normal behavior:
  • On Unity Loader, when M340 or PRA PLCs are NOCONF, the NOCONF state is displayed properly and does not get replaced by STOP after a few seconds.
  • On EADM, when an M580 PLC is NOCONF, the NOCONF state is displayed properly and does not get replaced by STOP after a few seconds.
Note:
  • The same behavior was observed on BMXPRA0100 (FW V3.51IR07) modules and on multiple FW versions of P34 2020:
  • V3.30IR10
  • V3.40IR08
  • V3.50IR08
  • V3.51IR07
This issue is planned to be fixed in EADM V3.3, Q2 2024.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings