Note: The NMC/Display FW update can be performed with the UPS output on
Potential Issue if encountered:
If a No UPS Communication Error occurs, refer to https://www.apc.com/us/en/faqs/FAQ000263669/ How to recover your Smart UPS Modular Ultra from a No UPS Communication Error
  
To inform customers on the procedure of upgrading the SUMU NMC/Display firmware using the USB Port
Product Line:
Smart UPS Modular Ultra
Environment:
All models, all serial numbers
Resolution:
Note: The NMC/Display FW update can be performed with the UPS output on
- Download the firmware upgrade file. Note: Always refer to the web site for UPS model and latest firmware.
 - Create a folder named apcfirm on the USB flash drive.
 - Extract the firmware file. 
- Double click then run the .exe file. The following window should open and deselect the option in the red box, then unzip.
 
- Close the WinZip extractor
 
- In the new folder created in the download directory, open the folder, and open the 'Bins' folder
 
- In the 'Bins' folder, copy just the '.nmc' file and place that file in the apcfirm directory
 
- Example 
 
 - Use a text editor to create a file named nmc3.rcf. (The file extension and text format must be .rcf, not .txt for example.)
 - In nmc3.rcf, add a line for the firmware package to be upgraded. 
- For example, to upgrade Smart-UPS application version v2.x, type: NMC3=apc_hw21_su_2-x.nmc3
 
 - Save the nmc3.rcf file in apcfirm folder. 
- In order to make sure the file is changed to a .rcf file, please follow the steps below: 
- In the folder where the "nmc3.rcf" file is saved, go to the 'View' tab and make sure "File name extensions" is checked. 
 -  Find the "nmc3.rcf.txt" file and rename it to just "nmc3.rcf".  Click yes. 
 -  The File Type should now show it as an "RCF File". 
 
 - In the folder where the "nmc3.rcf" file is saved, go to the 'View' tab and make sure "File name extensions" is checked. 
 
 - In order to make sure the file is changed to a .rcf file, please follow the steps below: 
 - Insert USB storage device containing NMC/Display firmware update into USB port located on the display 
 - Pop-up screen appears acknowledging connected USB storage device; touch OK to continue. The pop-up screen window is open for approx. 5 sec then disappears.
 - On the USB Storage screen that appears, select “Install NMC Display Firmware” and touch OK
 - Select Yes to continue the update process; select No to abort.  If yes is not touched quickly enough, the menu reverts back to the original message. 
- Wait for the NMC display to reboot; this will take a couple of minutes. The display will go blank
 - Status LED will illuminate amber during the update
 
 - Navigate to Home -> About -> Display -> right arrow to second window to verify the firmware Application version
 - Navigate to Home -> Configuration -> USB Storage and select Eject storage device when completed
 
Potential Issue if encountered:
If a No UPS Communication Error occurs, refer to https://www.apc.com/us/en/faqs/FAQ000263669/ How to recover your Smart UPS Modular Ultra from a No UPS Communication Error