How can we help you today?

Is the I-Line panelboard IP2X rated?

Product Line:

I-Line Panelboard

Environment:

Low Voltage Panelboard

Cause:

Need to verify if I-Line panels are IP2X rated.

Resolution:

No, IP2X is only available on NQ panelboard. I-line does not have IP2X offerings. I-Line panelboards have custom barrier offerings which can be selected through the product selectors and provides load side breaker lug shields and a barrier over the Neutral assembly. However, this does not have an official finger safe rating either.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings