Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Altivar and Altistart keypad connection in Modbus Serial port

Issue:

Does the VW3A1111 keypad can be connected in the Modbus serial port?

Product line:
Altivar Process, ATV630, ATV930, ATS480

Environment:
All models

Cause:
Costumer would like to know if it's possible to connect the keypad in the Modbus Serial port instead of connecting it on the front of the drive.

Resolution:
Yes, you can connect the keypad in the Modbus port, you only need to confirm the baud rate, the word order and the modbus format.
Baud rate: 19200bps
Terminal Modbus word order: Modbus Word Order ON
Modbus format: 8 bits even parity 1 stop bit

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings