How can we help you today?

Smart-UPS Ultra 5-10kVA output cannot be turned on using the NMC Web Interface shortly after a UPS firmware upgrade is performed

Issue: The UPS output cannot be turned on using the NMC Web Interface shortly after a UPS firmware upgrade is performed.

Product Line: SRTL5KRM2UI, SRTL5KRM2UT, SRTL8KRM4UI, SRTL8KRM4UT, SRTL10KRM4UI, SRTL10KRM4UT

Cause: After the UPS firmware upgrade is completed, the UPS requires approximately 3.5 minutes to boot and to connect the relevant internal components. This is expected behavior.

Resolution:

After the UPS firmware upgrade is completed successfully, wait at least 3.5 minutes before commanding the UPS to turn on using the NMC Web Interface.

Note: After the UPS firmware upgrade is completed, the UPS LCD will be booting for 2.5 minutes.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings