How can we help you today?

How to check the GOOSE simulation mode on the BMENOP0300 ?

There is a simulation mode dedicated to GOOSE communication between the BMENOP0300 module configured as client, and IED device servers.

It is activated by defaut in the IED device servers to avoid any damages when It is in a commisionning phase. When activated, the simulation mode is detected by the NOP module which will ignore automatically all GOOSE messages marked as "simulation".

We can check the GOOSE simulation status of the IED device servers on the BMENOP0300 module device DDT, inside the NOP_MODULE_MOD_INFO.CLIENT_STATE related to the IED device server. Example:

SIMULATION MODE:

Simulation Mode


NORMAL MODE:

Normal Mode

Schneider Electric USA

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings