Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
ATS480 tripping on PHF3 fault.
Issue:
Why does the ATS480 Softstarter trip on PHF3, Phase Loss Error after a run command?

Product Line:
ATS480

Environment:
All

Cause:
NA

Resolution:
PHF3 is Phase loss error. If the motor current in one or more phases is below the threshold set in [Phase Loss Thd] PHL parameter, the soft starter triggers the [Phase Loss] PHF3 error.
This PHL parameter is visible if [Phase Loss Monit] PHP is set to [Yes] YES.

Causes:
• Loss of one or several phases on mains or motor side
• Soft starter incorrectly supplied or tripped fuses.
• Defective motor
• Defective wiring on the motor or the supply mains

Remedy:
• Verify the threshold set in [Phase Loss Thd] PHL is compatible with the motor. Set PHL to 5% and try again.
• Verify the motor supply wiring and any devices located between the mains and the soft starter
(contactor, fuses, circuit-breaker,...)
• Verify the motor

Clearing the Error Code:
This detected error is automatically cleared with the [Auto Fault Reset] ATR or manually with the
[Fault Reset Assign] RSF parameter after its cause has been removed.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings