What is the MCOV rating for Model# 425480DP10AWAJ10?

Product Line:

ASCO Surge Device

Environment:

Surge Protection Device

Cause:

Need to confirm if the MCOV of Model# 425480DP10AWAJ10 is rated 115% above nominal voltage.

Resolution:

As per VPR chart on Page 2 shows an MCOV of 552V which is exactly 115% above nominal voltage. That is 480V x 1.15 = 552V.