What is the replacement for EE112T1814HFISNLP?

Issue:

Replacement for part number EE112T1814HFISNLP.

Product Line:

Low voltage Transformers

Answer:

This is something that would be built in SE Advantage/product selector. Please see the break down of the catalog:

EE-112-T-1814-HF-IS-NLP

EE is our transformer product line, Energy Efficient. This is replaced by our EX/EXNs.

112 - is for 112.5kVA

T - 3-phase

1814 - 480V Primary to 480Y/277V Secondary

HF - for 115 deg C Temp Rise

IS - Isolation Shield

NLP - Non-linear, K13 listed (this would be selected on the first part where it says EX/EXNs)