How many operations is an undervoltage trip rated for in a PowerPact H, J, or L frame breaker?

Product Line:
Molded Case Circuit Breaker

Resolution:

The UVR is rated for half the breaker's operations. Below are the amount of operations each breaker frame size is rated for.

Frame Size (A)Full Load OperationsNo Load Operations
0-1006,0004,000
101-2254,000

4,000

226-6001,0005,000