ECB24015G3 UL Regulation update
Issue:
Changes to UL Regulation for breaker testing requires update to ECB-G3 15A breaker label and documentation.
Product Line:
ECB-G3 15A one, two, and three pole
Environment:
ECB-G3
Cause:
UL Regulations that took effect in 2022, required a new test on the ECB24015G3 circuit breaker.
Resolution:
New label and documentation stating the 15 A ECB-G3 one, two, and three-pole products should not be used with 14 AWG wire. Use only 12 AWG or larger wire when wiring this device.
Date code: 24114
Note: Anything prior to this date does not require 12 AWG wire.