What's the signal wires size and specifications for SELV and Non-SELV?

Product line:
Three Phase UPS, Galaxy V Series

Environment:
GVS, GVM, GVL, GVX

Resolution:
All Class 2/SELV signal cables shall be double insulated/jacket cable and minimum rated for 30 VDC. All non-Class 2/non-SELV signal cables shall be double insulated/jacket cable and minimum rated for 600 VAC.

Signal cable sizes