Can I make a line-side tap connection from the Schneider Inverter to the Schneider Pulse CSED Panel?
No, you cannot make a line-side tap connection from the Schneider Inverter to the Schneider Pulse CSED Panel. Line-side tap connection requires that the wires from the inverter are connected to the service wires on the line side of the service disconnect. The inverter output circuit should be terminated on a circuit breaker installed on the bus bar inside the Pulse CSED.