How can we help you today?

Can you add QO GFI breakers to HQO206AC?

Issue: HQO GFI breakers

Product Line: Panelboards

Resolution:

They can not add any QO breaker that contains a pigtail to the HQO devices. This includes the GFI.

The HQO device has two metal support brackets that the front cover screws onto. When you try to install a pigtail breaker into this device, the breaker load screws come too close to those metal supports and can cause an arch to occur. Only standard QO breakers can be installed.

Schneider Electric USA

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings