Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How to upgrade your NMC2 & NMC3 firmware using the NMC Firmware Update Utility

Article available in these languages: French

Issue:
The customer asked how to upgrade the firmware through the utility tool.

Product line:
NMC2, NMC3

Environment:
AP9630, AP9631, AP9640 & AP9641

Cause:
Web interface displays a UPS "not recognized" error or the customer is installing a new NMC.

Resolution:
Please follow the next steps.
1. Access the Downloads page.

2. Locate firmware for the product by NMC model (ie AP9630).

(NOTE: Some products' firmware is not available on the download page. Contact Technical Support for support on products not found on the firmware download page.)

3. Run the application and enter the following information.

  1. Host (Ip address of the unit)
  2. UserName and Password of the NMC
  3. Click on Start Update

If you notice that the application stops with the selected protocol (SCP for this case) please try with FTP.
Firmware utility



Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings