Issue:
Can I-line panel be used on 240V open delta ?
Product Line:
I-line panelboard
Answer:
For I-line panelboard, using it in 240V open delta will not be an issue. There will be no restrictions as long as phase to phase voltage is 240V on all 3 phases and no neutral can be used.