Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Can I-line panel be used on 240V open delta system?

Issue:

Can I-line panel be used on 240V open delta ?

Product Line:

I-line panelboard

Answer:

For I-line panelboard, using it in 240V open delta will not be an issue. There will be no restrictions as long as phase to phase voltage is 240V on all 3 phases and no neutral can be used.

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings