How can we help you today?

Can I-line panel be used on 240V open delta system?

Issue:

Can I-line panel be used on 240V open delta ?

Product Line:

I-line panelboard

Answer:

For I-line panelboard, using it in 240V open delta will not be an issue. There will be no restrictions as long as phase to phase voltage is 240V on all 3 phases and no neutral can be used.

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings