How can we help you today?

Is there a bus bar extension kit for 600A NQ interior like the NQ484L6C to put (18) 2-pole 125A breakers?

Issue:

Wants to put 18 pcs of a QOB2125 in NQ484L6C

Product Line:

NQ Panelboard

Environment:

Application

Resolution:

The maximum number of 125A 2P breakers that can be installed in a 600A NQ interior is 5 due to neutral port restrictions

It is a misapplication of an NQ lighting panel. It should be an I-LINE panel.