Are the K13 rated transformers classified as "Harmonic Mitigating with 0-degree phase shift"

Product Line:

K-rated Energy Efficient Transformers

Environment:

Low Voltage Transformers

Cause:

Clarification on K13 transformers in relation to Harmonic Mitigating application.

Resolution:

No, the K13 transformers are 30 degree phase shift. The special HMT (Harmonic Mitigating) type Transformer products has been discontinued by Square D / Schneider Electric several years ago. They had specially wound secondaries and different phase shifts you could order. The K-rated Transformers are our only offer now for high harmonic applications.