Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
My UPS shows EPO Activated when the system enable switch is toggled

Article available in these languages: Spanish

Issue:
Smart-UPS Ultra 5-10kva displays "EPO Activated" when toggling the system enable switch

Product Line:
Smart-UPS Ultra 5-10kva models: SRTL5KRM2UI, SRTL5KRM2UT, SRTL8KRM4UI, SRTL8KRM4UT, SRTL10KRM4UI, SRTL10KRM4UT

Cause:
This is normal behavior from the UPS.  When the System Enable switch is toggled on the back of the UPS, "EPO Activated" alarm will show.

img1

Resolution:
Please press OK (checkmark) to clear the EPO alarm.

In order to properly perform a Logic Reset or Braindead on this UPS, please follow FAQ000267847.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings