What is the part number for the terminal block (adaptor) used for LRD4/LR2D4 overload relay to get it mounted on a LC1D115 & LC1D150 contactor?
Issue:
Is LA7D3058 required to mount LRD4 Overload relays on LC1D115 and LC1D150 Contactors?
Product Line:
Contactors and Starters - IEC
Environment:
Tesys D contactors
Resolution:
LRD4*** overload relays don't require any additional terminal blocks to mount directly onto LC1D115 and LC1D150 Contactors. The LRD4*** overload relay is shipped with the adaptor.
LRD4*** Overloads attach beneath the contactor directly.
However, should the adaptor become damaged or lost, the LA7D3058 adaptor is the replacement.
Is LA7D3058 required to mount LRD4 Overload relays on LC1D115 and LC1D150 Contactors?
Product Line:
Contactors and Starters - IEC
Environment:
Tesys D contactors
Resolution:
LRD4*** overload relays don't require any additional terminal blocks to mount directly onto LC1D115 and LC1D150 Contactors. The LRD4*** overload relay is shipped with the adaptor.
LRD4*** Overloads attach beneath the contactor directly.
However, should the adaptor become damaged or lost, the LA7D3058 adaptor is the replacement.