How can we help you today?

Temporarily Bypass Easy-UPS Registration

Some Easy-UPS Online UPS require a one time registration code during installation to allow the UPS output to be turned on. The customer or FSR will contact the Schneider Electric Customer Care Centre to register the UPS. Please see the user manual or the below FAQ on how to complete this registration.

Easy-UPS Registration

If for some reason you are unable to complete the registration, follow the below process on how to temporarily bypass the registration process.

Process:
1. After installation, turn on the Easy-UPS. The Easy-UPS display screen will display a three digit code along with the Online, On Battery, Bypass, and Alarm symbols.
Easy UPS Display Code 4

2. Press and hold the Power, Mute / Esc, Enter, Up, and Down buttons simultaneously for 5 seconds.
Easy UPS Display Code 5
Easy UPS Display Code 6

3. Once the buttons have been pressed for 5 seconds, the registration interface disappears and the normal interface appears.
Easy UPS Display Code 6

4. The Easy-UPS can now be used but as this is temporary solution,this process will have to be repeated once the UPS restarts until the UPS has been successfully registered.

Schneider Electric USA

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings