How many Current Transformers can be installed within MV Metal Clad Switchgear?

Article available in these languages:

  • Spanish

Issue:
Customers must be knowledgeable about the features and design of MV Metal Clad Switchgear to prevent errors and ensure it functions correctly to meet their requirements.

Product Line:
MV Switchgear.

Environment:
Metal Clad, VR Circuit Breaker.

Cause:
Maintenance and understanding the operation of the Metal Clad design.

Resolution:
Bushing-type, single- or multi-ratio Current Transformers can be mounted around either the top or bottom insulated tubes/Bell Assembly. A maximum of four Current Transformers can be mounted per phase, depending on the accuracy: For Standard Accuracy Current Transformers, two on the line side and two on the load side can be mounted. However, if High Accuracy Current Transformers are required, only one can be mounted on the line side and another on the load side.

Circuit Breaker Section without Circuit Breaker-Shutter Forced Open

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings