How can we help you today?

What's the terminal data for NF lug kit NFALM6?

Issue:

What's the terminal data for NF lug kit NFALM6.

Product Line:

NF Panelboards

Answer:

The lug kit can accommodate (2)1/0-750 kcmil Al or Cu

You can check this in the Digest Section 7 Table 9.152: NF Standard Mechanical Lugs—Main Lug page 9-68:

https://download.schneider-electric.com/files?p_Doc_Ref=0100CT1901_SEC-09&p_enDocType=Catalog&p_File_Name=0100CT1901_SEC-09.pdf

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings