What's the terminal data for NF lug kit NFALM6?

Issue:

What's the terminal data for NF lug kit NFALM6.

Product Line:

NF Panelboards

Answer:

The lug kit can accommodate (2)1/0-750 kcmil Al or Cu

You can check this in the Digest Section 7 Table 9.152: NF Standard Mechanical Lugs—Main Lug page 9-68:

https://download.schneider-electric.com/files?p_Doc_Ref=0100CT1901_SEC-09&p_enDocType=Catalog&p_File_Name=0100CT1901_SEC-09.pdf