What are the altitude correction factors for Metal Clad Switchgear?

Article available in these languages: Spanish

Issue:
Metal Clad Switchgear operated at altitudes above 1000 m / 3300 ft should be multiplied by correction factors to obtain the desired performance.

Product Line:
MV Switchgear.

Environment:
Metal Clad.

Cause:
To achieve the desired performance from Metal Clad Switchgear.

Resolution:
Switchgear assemblies that depend on air for an insulating and cooling medium will have a higher temperature rise and a lower dielectric withstand capability when operated at altitudes above 1000 m / 3300 ft. For applications at higher altitudes, the rated power frequency withstand voltage (1 min), the lightning impulse withstand voltage (BIL), and the continuous current rating of the assemblies should be multiplied by the correction factors in the following table to obtain the modified maximum limits for dielectric withstand and continuous current.
Altitude (m)Altitude (ft)ACF for dielectric
withstand voltage
ACF for continuous
current
1000330011
120040000.980.995
150050000.950.991
180060000.920.987
200066000.910.985
210070000.890.98
240080000.860.97
270090000.830.965
3000100000.80.96
3600120000.750.95
4000130000.720.94
4300140000.70.935
4900160000.650.925
5500180000.610.91
6000200000.560.9
IEEE Std C37.20.2™-2015

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings