How to correct the Scadapack Workbench Error 0046: Insufficient reserved memory size for temporary variables
  • Increase the memory size in the Scadapack Workbench program.
  • Under the program name in solution explorer, go to properties>Memory size, see details below.
    SW_Insufficient memory

    Run the Memshow to check how many free NVram memory you have.
  • Connect to SCADAPack using SCADAPack E configurator
  • Under Transfer menu, select Remote Command Line.
    SW_Insufficient memory2


  • Then Type command Memshow, it displays information related to system memory, see details below
    SW_Insufficient memory3