Is there a parallel lugs for 4/0 wire for QMJ365 disconnect?
Issue:
Optional lugs for QMJ365
Product Line:
Panelboard
Environment:
QMB/QMJ
Resolution:
The QMJ365 as standard only allows for (1) 1/0-750kcmil Al/Cu. NO alternate lugs are available to allow for either larger wires or more cables. The only potential optional lug would be a compression lug. To get (2) wires per phase using compression lugs, it will require, using (2) VCEL05012H1 good for (2) 1/0–300 (Al/Cu) kcmil'