Is there a parallel lugs for 4/0 wire for QMJ365 disconnect?

Issue:

Optional lugs for QMJ365

Product Line:

Panelboard

Environment:

QMB/QMJ

Resolution:

The QMJ365 as standard only allows for (1) 1/0-750kcmil Al/Cu. NO alternate lugs are available to allow for either larger wires or more cables. The only potential optional lug would be a compression lug. To get (2) wires per phase using compression lugs, it will require, using (2) VCEL05012H1 good for (2) 1/0–300 (Al/Cu) kcmil'

Schneider Electric USA