PME - "A valid server license could not be found" error
Issue
Customer receives a report they are getting an alert that a valid server license could not be found, and that communication with devices will be suspended after a certain number of days. However the customer does indeed have a valid server license.
Product Line
EcoStruxure Power Monitoring Expert
Resolution
One possible root cause of this issue is that the ION Site Service is starting before the Core Services when restarting the server that PME is installed on. Normally in the process of the server starting up, the Core Services starts up before ION Site Service. Core Services is responsible for the Licenses attributed to PME.
This means that ION Site Service is not able to obtain the licenses that are on the server machine, throwing up the "No License" error information. However, when Core Services started, they were able to fetch the licenses properly.
To solve this issue apply a Delayed Start to ION Site Service.