Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Is it possible to field install a Voltage Presence Indicating System (VPIS) in my existing RM6 GIS switchgear?

Issue:

Customer planning to install VPIS on their installed RM6 on-site.

Product Line:

MV Gas Insulated Switchgear.

Environment:

RM6.

Resolution:

It is a very complex activity to install VPIS on-site from scratch, which involves proper wire harnessing and testing for verification and validation. This is not a job which a customer can do on their own on-site. VPIS supplied on RM6 cubicles are factory fitted as per the specifications on ordering. Please reach out to Schneider Electric Field Services for this activity. Schneider Electric only recommends customer to replace an existing VPIS on-site. See attached adaptation instructions which are surely not for doing on-site installation without experience.

Schneider Electric USA

Attachment(s)
BBV3402401_05(web)_RM6.pdf [1.99 MB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings