How can we help you today?

When is a 3-point latch system required in a panelboard?

Issue:

A customer wanted to know if we can use NC74VS, instead of NC74VS3PNF in panels. Is there any reason why the L-frame needs the 3-point latch?


Product Line:

NQ/NF Panelboards


Environment:

Application


Cause:

Product Features


Resolution:


The PowerPact L frame main breaker interior requires the trim with the 3-point latch to meet the short circuit testing.

The vented trims with the 3-point latch vault handle are required when the main breaker is a PowerPact L frame.\

If you are using an L-frame Main breaker. You can't use the standard trim it has to be a 3-point latch


UL Short Circuit Testing dictates which locking system is required to meet their test criteria.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings