How can we help you today?

PME2024 TGML Component Binding

Issue Description:
TGML component binding is not working in PME2024.

Environment:
PME Graphic Designer

Cause:
The binding property was changed in PME 2024, which prevents the use of component binding.

Component Binding

Below error will appear in the web application:

Web App Error

Resolution:
Follow these steps to fix the component binding issue:

  1. Navigate to the PME installation folder.
  2. Open app.js from this location: Applications\\SystemDataService\\Content\\Applications\\Diagrams\\Scripts\\TGMLviewer.
  3. Search for bindings[bindFullName] = bindName; in app.js.
  4. Comment out bindings[bindFullName] = bindName;. Workaround
  5. Save app.js.
  6. Perform an IIS reset and refresh the PME web application.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings