Product Line:
Thermal Management Systems/ ClimaSys
Environment:
ClimaSys CC Temperature Controller
Cause:
How to Install and wire correctly the electronic hygrotherm controllers
Resolution:
Hygrotherm work in 3 different profiles, (M1 /M2 /M3) M1 by default
Depending on the operating mode the controller will work with 2 Loads that will either require Fan systems/ Resistances/Alarms/Probes to be connected to act as LOAD 1 and LOAD 2
Wiring Diagram linked to Operating Mode
According to the respective operating mode our Load will need to be connected as follow:
M1/M3
Load1 = fan, Load2 = resistor
M2
Load1 = resistor, Load2 = resistor/alarm
Probe1 = temperature -40...+ 90 ºC
Probe (accessory as an option, code NSYCCASTE)