Product Line:
Industrial Automation Control
Environment:
Motor Management Systems TeSys T
Cause:
How to Enter/Exit configuration mode on the TeSys T via SoMove and save modified parameters on the LTMR controller
Resolution:
Configuration Mode it´s a state on which the controller (LTMR) will allow us to freely modify and change parameters and configuration setting on the current connected controller, for this it is mandatory that a correct communication has been established, and that out program data is currently synchronized.
Once our data is synchronized and a stable communication path has been made with the LTMR and SoMove we will have a READY state showed on the foot of the software.
To enter configuration mode, we will click on our top tab that called DEVICE -> COMMAND -> ENTER CONFIGURATION
We can confirm that we entered configuration mode successfully if our READY state has been changed to In Config
Entering this state will unlock all parameter setting to be changes and modified as needed, once our changes are made and we´re ready to load them into the controller, we will exit configuration mode on the same path DEVICE -> COMMAND -> Exit Configuration Mode -> Yes
After confirming exiting configuration mode our device state will go back to READY state after a brief moment and changes will be done to the program, we suggest doing a last Load to Device in order to match any modification SoMove <-> Controller.