Maximum distance for input logic connections on TeSys T LTMR devices

Issue:
What is the maximum distance for input logic connections on TeSys T LTMR devices

Product Line:
TeSys T LTMR Motor Management Controller


Environment:
NEMA and IEC Starters protection components


Cause:
Long wire distances can create EMC disturbance effects on the LTMR controller.


Resolution:
The maximum distance allowed without interposing relay is addressed below:

Wire Size

1 mm2 (AWG 18)

1.5 mm2 (AWG 16)2 mm2 (AWG 14)2.5 mm2 (AWG 14)
Maximum distance for wires 210 m (689 ft)182 m (597 ft)163 m (535 ft)149 m (489 ft)

However, due to variability of installations it is highly recommended to use interposing relays for control cable lengths longer than 100 m (328 ft).