How can we help you today?

Configuring x70 RTU Object in GeoSCADA For RTZ Import/Export

To configure the x70 RTU object in GeoSCADA, follow the steps outlined: *Note: This example will follow the setup using DNP3.

  • Set up the direct DNP3 outstation set, and channel as normal. The outstation will need to be a SCADAPack DNP3 direct outstation:

Outstation object location

  • Create a new RTU object depending on the SCADAPack being used:

RTU object location

  • Within the properties of the outstation created, there will be a 'SCADAPack x70' tab; within it, input the newly created device into the 'SCADAPack x70 Device' field.

image1

  • Ensure all created objects are in service, and you will now be able to import the RTZ file from RemoteConnect into GeoSCADA.

image2

Schneider Electric USA

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings