Zelio Smart Relay: Program Construction Error

Issue:

ZelioSoft 2 shows the "Prorgram construction error" when transferring the program from the relay to the PC.

Product Line:

Relays and Timers

Environment:

Zelio SR2 and SR3 Smart Relays

Resolution:

There are certain cases where the program cannot be retrieved and Zeliosoft 2 shows the following "Program construction" error:

Program construction error message

ZelioSoft should rebuild the application with following limitations:

  • Construction using the file specified by the user: enter the file path of the application to be retrieved.
  • Automatic construction of the program: In this case, the Programming Software regenerates the application from the data retrieved on the smart relay.
NOTE: The program loaded into the smart relay does not contain information concerning page setup (drawing, comment, relative position of the function blocks and links); a default page setup is thus produced.