{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
M580 and WRITE_PARM with EHC modules

Question: Can module parameters such as Modulo be programmatically changed when using high speed counter modules?

Answer: No, this is a limitation when the counter modules are mapped as Device DDT using Control Expert.

With the M580 incorporating Device DDT mapping, the adjustment parameters cannot be changed from the PLC application during operation (no support of READ_PARAM, WRITE_PARAM, SAVE_PARAM, RESTORE_PARAM) for:

  • counter modules in a Quantum EIO drop
  • counter modules in a M580 RIO drop

Schneider Electric USA

Explore more
Product:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Product: