How can we help you today?

ION Meters "Potential Security Risk: Detected an Invalid security certificate in use" shown in ION Setup

!!!Confidential Content

Issue

The following error is shown when an ION meter is opened in ION Setup using single device mode:

ION Setup Pop up window "Potential Security Risk: Certificate Error Summary"

"Potential Security Risk. Certificate Error Summary. Detected an invalid security certificate in use. Certificate has expired. The certificate is not trusted because it is self-signed. Error code: RemoteCertificateNameMismatch, RemoteCertificateChainErrors. The security certificate is not trusted by your computer's operating system. This may be caused by a misconfiguration or an attacker intercepting your connection. Only press Proceed if you are sure the connection is secure."

Product Line

ION Meters

Environment

ION Setup

Cause

This message is caused when a meter is configured to use Secure ION, or ION over TLS. By default, devices that support Secure ION include a self-signed SSL certificate. If using ION Setup single device mode, you must accept the certificate every time you connect to the device using ION Setup.

Resolution

To increase security and prevent this message from re-appearing in single device mode, use a Certificate Authority (CA). This can be provided by IT.

For more information on secure ION, see the PM8000 online guide https://product-help.schneider-electric.com/PowerLogic-PM8000/en-us/content/03-communications/secure-ion.htm?tocpath=Communications|ION|Secure ION|_____0

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings