How can we help you today?

Power Monitoring Expert Installer Fails at Create Database Folder step due to Access is Denied error

Issue:

PME Installer gives user "access is denied" error at the Create Database Folder step.

Product Line:

Power Monitoring Expert 2023

Power Monitoring Expert 2024

Environment:

Power Monitoring Expert Installer

Cause:

PME Folder reverts back to Read-Only even after unselecting the option for the PME Folder properties.

Resolution:

  1. Navigate to the File Explorer
  2. Go to the File path where you have selected the PME folder to be placed during installation.

NOTE: File path should be similar to this example: C:\Program Files (x86) \Schneider Electric

  1. Navigate to the Power Monitoring Expert Folder
  2. Right-click the folder and select Properties
  3. Navigate to the Security Tab
  4. Once in Security select a user from the Groups and User Names option
  5. Select Edit and in the Permissions box select Full Control
  6. Select Apply and OK
  7. Repeat steps 6-9 for all users found in the Groups and User Names section
  8. Once all users have Full Control of the PME folder navigate back to the PME installer
  9. Re-run the failed Created Database Folder step and the installer should finish this step successfully

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings