Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Do Q23225NRB and L600AWK comes with lug covers?

Issue:

Do Q23225NRB and L600AWK comes with lug covers?

Product Line:

Molded Case Circuit Breakers

Answer:

No, it has to be purchased separately.

For Q frame like the QGL, see FAQ: https://www.se.com/us/en/faqs/FA118945/

For L frame like the LGL, see FAQ: https://www.se.com/us/en/faqs/FA239883/

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings