PME 2024- Tamper detected error. A valid software license could not be found.

Product Line
Power Monitoring Expert 2024
_____________________________________________________________
Environment
License Configuration Tool
_____________________________________________________________
Issue :
A valid software license could not be found.
A valid license could not be found

The system logs are flooded with the error: Tamper detected: FlxDotNetClient.SvcSessionException: MID=0, SID=0, EID=6

_____________________________________________________________
Proposed Solution

Solution 1:

Import the attached 3 certificates to the Trusted Root Certification Authority through the Manage Computer Certificates interface.

  1. VeriSign Universal Root Certification Authority.cer
  2. VeriSign Class 3 Public Primary Certification Authority - G5.cer

DigiCert Trusted Root G4.cer

Trusted Root Certification

Then run the below PowerShell script after getting the exported certificate in the system.

Change the path of the exported file in the following script and run it in PowerShell ISE in administrator mode.

$sst = ( Get-ChildItem -Path C:\certs\roots.sst )

$sst| Import-Certificate -CertStoreLocation Cert:\LocalMachine\Root

Solution 2:
If the previous solution fails, rebuild the certificate chain using a functioning PME system.

From this working PME system, export the three specified certificates. You can find the link below to export the trusted root certificate from the functioning machine.
http://woshub.com/updating-trusted-root-certificates-in-windows-10/

Then run the below PowerShell script in the non-working system after getting the exported certificate in the system:

Change the path of the exported file in the following script and run it in PowerShell ISE in administrator mode

$sst = ( Get-ChildItem -Path C:\certs\roots.sst )

$sst| Import-Certificate -CertStoreLocation Cert:\LocalMachine\Root

Schneider Electric USA

Attachment(s)
VeriSign Universal Root Certification Authority.cer [1.18 KB]
VeriSign Class 3 Public Primary Certification Authority - G5.cer [1.21 KB]
DigiCert Trusted Root G4.cer [1.39 KB]
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings